Home > Water Quality Products > B20 Recording Chlorine Monitor
B20 Recording Chlorine Monitor from ATI
 |
Providing permanent chlorine residual records normally means purchasing a residual chlorine monitor and connecting the output of the monitor to a separate recorder. ATI's Series B20 provides an integrated solution to this problem, combining both the analyzer and recorder functions in a single package. This means simpler installation, easier operation and lower cost. And best of all, the system uses a direct measuring membraned sensor for reliable measurement with minimal maintenance. |
|
Series B20 chlorine recorders use the same reliable chlorine sensor supplied for years as part of the Series A15 monitoring systems. The sensor is a direct measuring polarographic membraned sensor that eliminates the need for chemical buffers and other reagents. Sensors are available for free chlorine measurements or for combined chlorine monitoring where chloramine treatment is in use.
Chlorine sensors require a constant sample flow past the membrane to provide stable and accurate readings. B20 systems are supplied with a constant head flowcell assembly that automatically maintains the desired flow. Hose barbs for sample inlet and drain provide for connection of flexible PVC tubing.
|
|
Specifications
| Range |
0-1 to 0-5 ppm or 0-5 to 0-20 ppm |
| Chart |
10" with 0-100% scale, 24 hour scale, package of 100 |
| Chart Speed |
Selectable for 24 hour or 7 day |
| Display |
Digital concentration display |
| Accuracy |
+/- 0.05 ppm |
| Repeatability |
+/- 0.02 ppm |
| Response Time |
90% in 60 seconds |
| Enclosure |
NEMA 3 Noryl, acrylic window |
| Sensor |
Polarographic membraned type |
| Sensor Materials |
Noryl and stainless steel |
| Sensor Cable |
25' standard, 100' maximum |
| Flowcell |
Constant head overflow type |
| Flowcell Materials |
Clear acrylic, stainless plate |
| Inlet |
1/4" id tubing hose barb (1/8" FNPT) |
| Drain |
1/2" id tubing hose barb (3/8" FNPT) |
| Sample Flowrate |
15 GPH (7 GPH minimum) |
| Sample Temperature |
0-50°C |
| Power |
120 or 240 VAC, 50/60 Hz, 9 watts |
| Flowcell Size |
4.5" W x 7" H x 3.5" D |
| Recorder Size |
14" W x 7" H x 3.5" D |
| Alarms |
Two programmable alarms |
| Alarm Relays |
Two SPDT, 5A @ 120 VAC resistive |
Ordering Information
For pricing information, please contact AFC International at 800-952-3293, 219-987-6825 or fax 219-987-6826 or email sales@afcintl.com.
| Description |
Catalog No.
|
| Series B20 Free Chlorine Recorder, Internal Amplifier, Sensor w/Clear Flowcell, 0-1 or 0-5 ppm |
B20/62-1-1-2
|
| Series B20 Free Chlorine Recorder, External Amplifier, Sensor w/Clear Flowcell, 0-1 or 0-5 ppm |
B20/62-2-1-2
|
| Series B20 Chloramines Recorder, Internal Amplifier, Sensor w/Clear Flowcell, 0-1 or 0-5 ppm |
B20/63-1-1-2
|
| Series B20 Chloramines Recorder, External Amplifier, Sensor w/Clear Flowcell, 0-1 or 0-5 ppm |
B20/63-2-1-2
|
| Series B20 Chloramines Recorder, Internal Amplifier, Submersible Sensor, 0-1 or 0-5 ppm |
B20/63-1-1-1
|
| Series B20 Chloramines Recorder, External Amplifier, Submersible Sensor, 0-1 or 0-5 ppm |
B20/63-2-1-2
|
|
|
Features
Free or combined chlorine recording
Selectable 24 hour or 7 day chart
Modular sensor for easy service
Digital concentration display
NEMA 3 wall or panel mount enclosure
Replaceable felt tip chart pens
Direct measuring chlorine sensor
No chemical reagents required
Simple constant head flowcell
Two alarm standard
|