E-mail this product to a friend
|
Series B14 - Gas Detection System Controller
The Series B14 Receivers are compact electronic modules that provide local alarm, display and signal retransmission functions for gas detection systems. The modules are designed to accept input from either two, three or four wire 4-20 mA transmitters located up to 10,000 feet from the receiver. They are ideally suited for use with ATI's Series A12 or B12 two wire toxic gas transmitter or Model B12-17 three wire transmitter combustible gas transmitter.

- LED Display - Gas concentrations are indicated in ppm, ppb, percent, or % LEL with the display range selectable by the user.
- Three Alarm Setpoints - Each module provides separate caution, warning and alarm setpoints with LED bar indicators of each point. LED indicators flash on initial alarm condition and change to steady on when the alarm is indicated.
- Signal Retransmission - A 4-20 mA output is provided from each module, optically isolated from the input signal to avoid ground fault problems.
- Three Relay Outputs - Modules contain individual alarm relays for each alarm setpoint. However, each relay can be assigned to any setpoint to allow multiple alarm functions at a single alarm point. Relays are configurable for either standard or fail-safe operation and for either latching or on-latching operation.
- Separate Trouble Alarm - A fourth LED alarm bar and relay are provided to indicate trouble conditions. The trouble alarm and relay will activate on loss of input signal or it the 4-20 mA input drops below a specific value.
- Remote Reset Input - Isolated input contracts are provided to allow an unpowered switch input for acknowledgment of alarm conditions from a remote location or via telemetry equipment.
- Internal Transmitter Power - Modules provide a 24 VDC power supply to operate either 2 or 3 wire transmitters.
- 12 VDC Powered - B14 modules are powered from a 12 VDC power supply available as an option. Up to 3 modules can be powered from one power supply (or 2 if battery backup is used).
Specifications
| Concentration Display |
4 Digit LED, programmable range |
| Input |
2, 3 or 4-wire 4-20 mA transmitter |
| Output |
Isolated 4-20 mA, 1,000 ohms maximum load |
| Power |
0-15 VDC, 250 mA maximum |
| Concentration Alarms |
Three adjustable concentration alarms.
Setpoints adjustable from 5-100% of span |
| Alarm Indicators |
LED bars for Caution, Warning and Alarm |
| Indicator Function |
Caution and Warning indicator non-latching. Alarm indicator latching |
| Alarm Relays |
Three assignable relays, 7 A, 120 VAC (4 A, 220 VAC) resistive.
Alarms are assignable to any one of three programmable setpoints |
| Relay Function |
Configurable for Normal/Fail-safe Latching/Non-latching, 2/second/10 second delay, or external horn function |
| Trouble Function |
Front panel, LED bar indicator and SPDT, 7 A relay.
Factory set for fail-safe operation |
| Alarm & Relay Reset |
Activated from front panel switch or through remote reset switch |
| External Reset |
Input terminals provided for unpowered contact input |
| Gas Indicator |
LED bar on front panel with gas symbol overlay |
| Electrical Connections |
Quick disconnect pluggable terminal blocks |
| Module Enclosure |
Noryl |
| Module Mounting |
Mounts to 35 x 7.5mm DIN rail |
Ordering Information
For pricing, please call AFC International at 1-800-952-3293, 219-987-6825 or fax 219-987-6826 or email sales@afcintl.com.
Downloads
B14 Literature
|