Home > Gas Detection > Fixed Point Gas Detection Systems > Millennium Carbon Dioxide Gas Detector

SEC Millennium Infrared
Carbon Dioxide Gas Detector

CO2 Infrared Transmitter

The SEC infrared carbon dioxide detector is a single source dual wavelength instrument. The sensing and reference elements are self-compensating for optical integrity and other signal inhibitors. The industry standard 4-20 mA analog output provides remote alarm, fault and calibration signals.

Features

  • Infrared sensing technology
  • Virtually maintenance free
  • Low cost of ownership, over five years operating life
  • Immune to poisoning and etching
  • Designed for harsh environments
  • Explosion proof
  • Compact, lightweight
  • Fast response time
  • Smart calibration
  • Self compensating optical bench and no moving parts
  • Heated optical chamber
  • Low power consumption
  • Operates in anaerobic atmosphere
  • Fault indications for all failure states
  • Routine calibrations are not required
  • 4-20 mA output
  • Many ranges available
  • RS-485 communication link
  • Digital display optional

Applications

The SEC Millennium detectors are designed to be used where a rugged, explosion proof, ultra reliable device is required.
  • Gas storage
  • Injection oil recovery
  • Industrial process control
  • Food processing & packaging
  • Greenhouses
  • Bottling plants
  • Water industry
  • Environmental chambers
  • Laboratories
  • Breweries & wineries
  • HVAC (DCV, energy management)
  • Engine test cells

Unit Status Chart

Current
Output
Status
4-20
mA
Normal measuring mode
0.0
mA
Unit fault
0.2
mA
Reference channel fault
0.4
mA
Analytical channel fault
0.8
mA
Unit warm up
1.0
mA
Optics fault
1.2
mA
Zero drift fault
1.6
mA
Calibration fault
2.0
mA
Unit spanning
2.2
mA
Unit zeroing
4.0
mA
Zero gas level
5.6
mA
10% of full scale
8.0
mA
25% of full scale
12
mA
50% of full scale
16
mA
75% of full scale
20
mA
100% of full scale
20.1-23
mA
Over range (>100%)

Specifications

Detectable Gases Carbon dioxide
Range 0-1% Volume
0-2% Volume
0-5% Volume
Alternate ranges are available
Accuracy +/- 3% 0 to 50% full scale
+/- 5% 51 to 100% full scale
Operating Voltage 18-36 VDC
Power Consumption 4 watts at 24 VDC
Analog Output 4-20 mA (sourced)
Response Time T50 < 3 seconds
T90 < 5 seconds
Humidity 0-99%, non-condensing
EMI Protection Complies with: C22.2 No. 152-M1984, ISA S 12.13.01-2000
Operating Temperature -40°F to 158°F
Enclosure 316 Stainless Steel
Classification Class I, Div I, Groups B, C, D

Ordering Information

For pricing, please call AFC International at 1-800-952-3293, 219-987-6825 or fax 219-987-6826 or email sales@afcintl.com.

Download a copy of the Millennium CO2 literature.

New Products | Air Sampling | Gas Detection | Other Meters | Respiratory | Water Quality | WMD HazMat
Applications | Product Specials | Rentals | Links | Index | Contact Us | Home


AFC International, Inc.
PO Box 894, DeMotte, IN 46310
715 SW Almond St, Ste C, DeMotte, IN 46310
800-952-3293 219-987-6825 Fax 219-987-6826
eMail: sales@afcintl.com

Last Revised: 1/23/07