SEC Millennium Infrared Carbon Dioxide Gas Detector

CO2 Infrared Transmitter

The SEC infrared carbon dioxide detector is a single source dual wavelength instrument. The sensing and reference elements are self-compensating for optical integrity and other signal inhibitors. The industry standard 4-20 mA analog output provides remote alarm, fault and calibration signals.

Unit Status Chart

Current
Output
Status
4-20
mA
Normal measuring mode
0.0
mA
Unit fault
0.2
mA
Reference channel fault
0.4
mA
Analytical channel fault
0.8
mA
Unit warm up
1.0
mA
Optics fault
1.2
mA
Zero drift fault
1.6
mA
Calibration fault
2.0
mA
Unit spanning
2.2
mA
Unit zeroing
4.0
mA
Zero gas level
5.6
mA
10% of full scale
8.0
mA
25% of full scale
12
mA
50% of full scale
16
mA
75% of full scale
20
mA
100% of full scale
20.1-23
mA
Over range (>100%)

Specifications

Detectable Gases Carbon dioxide
Range 0-1% Volume
0-2% Volume
0-5% Volume
Alternate ranges are available
Accuracy +/- 3% 0 to 50% full scale
+/- 5% 51 to 100% full scale
Operating Voltage 18-36 VDC
Power Consumption 4 watts at 24 VDC
Analog Output 4-20 mA (sourced)
Response Time T50 < 3 seconds
T90 < 5 seconds
Humidity 0-99%, non-condensing
EMI Protection Complies with: C22.2 No. 152-M1984, ISA S 12.13.01-2000
Operating Temperature -40°F to 158°F
Enclosure 316 Stainless Steel
Classification Class I, Div I, Groups B, C, D

Ordering Information

For pricing, please call AFC International at 1-800-952-3293, 219-987-6825 or fax 219-987-6826 or email sales@afcintl.com.

Downloads

Millennium CO2 literature.

Features

Infrared sensing technology

Virtually maintenance free

Low cost of ownership, over five years operating life

Immune to poisoning and etching

Designed for harsh environments

Explosion proof

Compact, lightweight

Fast response time

Smart calibration

Self compensating optical bench and no moving parts

Heated optical chamber

Low power consumption

Operates in anaerobic atmosphere

Fault indications for all failure states

Routine calibrations are not required

4-20 mA output

Many ranges available

RS-485 communication link

Digital display optional

Applications

Gas storage

Injection oil recovery

Industrial process control

Food processing & packaging

Greenhouses

Bottling plants

Water industry

Environmental chambers

Laboratories

Breweries & wineries

HVAC (DCV, energy management)

Engine test cells